四川少妇bbbb,日产精品久久久久久久性色,黑人糟蹋人妻HD中文字幕,日韩女人性开放视频

Leave Your Message
*姓名不能為空!
* 留言?xún)?nèi)容不能為空!
Product
Recommended products

One-control two-fan controller

This series of two-speed fan controllers is a high-performance product specially launched in response to market demand for low-power fans below 22KW. It is mainly used for smoke exhaust, fire control, etc.

    product detail

    Product overview

    This series of two-speed fan controllers is a high-performance product specially launched in response to market demand for low-power fans below 22KW. It is mainly used for smoke exhaust, fire control, etc.

    Wiring port description

    Terminal number

    illustrate

    Terminal number

    illustrate

    1

    Working power supply AC220V live wire

    11

    #Fan fire damper contact/connect normally closed

    2

    Working power supply AC220V neutral line

    12

    2# fan fire damper contact/normally closed

    3

    1# fan contactor coil control point

    13

    1# fan remote start and stop (automatic state)

    4

    2# fan contactor coil control point

    14

    2# fan remote start and stop (automatic state)

    5

    1# fan manual feedback point

    15

    1# fan forced start and stop (any state)

    6

    1# fan automatic feedback point

    16

    2# fan forced start and stop (any state)

    7

    Public terminal (passive)

    17

    1# fan fault protection point/normally open and normally closed programmable

    8

    2# fan automatic feedback point

    18

    2# fan fault protection point/normally open and normally closed programmable

    9

    2# fan manual feedback point

    19/20

    1# fan DC24V fire block starts when power is supplied and stops when power is lost (any state)

    10

    Public signal control terminal

    21/22

    2# fan DC24V fire block starts when power is supplied and stops when power is lost (any state)

    Automatic signal wiring

    Fire damper: connected to 8#, 9# and 8#, 10# (connected to normally closed);

    Remote control: connect 8#, 11# and 8#, 12# (start when connected, stop when disconnected)

    Fire center control (no protection if there is a fault): Connect 17#, 18# and 19#, 20# (DC24V has no positive or negative distinction)

    Forced start control (no protection if fault occurs): connect 8#, 13# and 8#, 14# (passive short circuit)

    Function selection instructions

    Power-off memory saving function

    This product has a power-off memory saving function. When the power is turned on again after a power outage, it will default to the state before the power outage. For example: when it is in manual state, the power is off, and when it is powered on, it is in manual state.

    Fault type selection

    In the automatic state, press and hold the 1# fan start button for more than 5 seconds to switch the fault signal type of terminals 15# and 16#, which are divided into normally open type and normally closed type. The factory default is normally open type.

    Protection type selection

    In the automatic state, press and hold the 2# fan start button for more than 5 seconds to change the fault protection type of the 15# and 16# terminals to the fault alarm type. It only alarms but does not disconnect the output, and switches the fault protection types in sequence.

    Wiring schematic diagram

    One control two fans controller.jpg

    Dimensional drawing

    One control two fans controller 1.jpg